The portable, one-piece PGK 80 high-voltage test device for generating negative DC voltage up to 80 kV is primarily used for onsite testing of paper-insulated mass-impregnated cables in the medium-voltage network. The high voltage is generated through a high-voltage transformer with secondary voltage-multiplier. The internal operating frequency of 20 kHz enables the smallest of device dimensions.
Features:
- stepless adjustable output voltage
- voltage measurement is made directly at high voltage output
- timer 1-30 min
- sensitive current measurement for acquisition of smallest insulation currents (6 ranges)
- high short-circuit current
- safety control according to VDE 0104
- transient wave protection
- socket for safety contact, emergency off switch, external signal lamps connection of Y/t plotter for recording the current output